LADN22

LADN22 – TeSys D – auxiliary contact block – 2 NO + 2 NC – screw-clamps terminals.

$30.00

LADN22

Category

Descripción

Main
range of product
TeSys F
TeSys D control relay
TeSys D
range
TeSys
device short name
LADN
product or component type
Auxiliary contact block
range compatibility
TeSys D LC1D contactor
auxiliary contacts operation
Instantaneous
pole contact composition
2 NO + 2 NC
connections – terminals
Screw clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end
Screw clamp terminals 1 cable(s) 1…2.5 mm²flexible without cable end
Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible without cable end
Screw clamp terminals 1 cable(s) 1…2.5 mm²solid with cable end
Screw clamp terminals 1 cable(s) 1…2.5 mm²solid without cable end
Screw clamp terminals 2 cable(s) 1…2.5 mm²solid with cable end
Screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end
Complementary
mounting location
Front
[Ui] rated insulation voltage
600 V – certifications UL
690 V conforming to IEC 60947-5-1
600 V – certifications CSA
[Ue] rated operational voltage
690 V AC 25…400 Hz
[Ith] conventional free air thermal current
10 A (at 60 °C)
Irms rated making capacity
140 A at <= 690 V AC conforming to IEC 60947-5-1
250 A at <= 690 V DC conforming to IEC 60947-5-1
permissible short-time rating
100 A 60 °C 1 s
120 A 60 °C 500 ms
140 A 60 °C 100 ms
protection type
GG fuse 10 A rating according to operational current for Ue <= 690 V
associated fuse rating
10 A gG conforming to IEC 60947-5-1
mechanical durability
30 Mcycles
minimum switching current
5 mA
minimum switching voltage
17 V
non-overlap time
1.5 ms on de-energisation no overlap between NC and NO contact
1.5 ms on energisation no overlap between NC and NO contact
overlap time
1.5 ms
insulation resistance
> 10 MOhm
product weight
0.05 kg

Información adicional

Peso 0.14 lbs