RE7ML11BU

RE7ML11BU – Time delay relay 6 functions – 0.05..1 s – 24 V AC DC – 1OC.

$145.00

RE7ML11BU

Category

Descripción

Main
range of product
Zelio Time
product or component type
Industrial timing relay
component name
RE7
time delay type
Di
D
W
C
A
H
time delay range
0.05 s…300 h
Complementary
discrete output type
Relay
contacts material
90/10 silver nickel contacts
width pitch dimension
22.5 mm
[Us] rated supply voltage
110…240 V AC 50/60 Hz
24 V AC/DC 50/60 Hz
42…48 V AC/DC 50/60 Hz
voltage range
0.85…1.1 Us
connections – terminals
Screw terminals, 2 x 1.5 mm² flexible with cable end
Screw terminals, 2 x 2.5 mm² flexible without cable end
tightening torque
0.6…1.1 N.m
setting accuracy of time delay
+/- 10 % of full scale
repeat accuracy
+/- 0.2 %
temperature drift
< 0.07 %/°C
voltage drift
< 0.2 %/V
minimum pulse duration
20 ms
reset time
50 ms
maximum switching voltage
250 V AC/DC
mechanical durability
20000000 cycles
[Ith] conventional free air thermal current
8 A
maximum [Ie] rated operational current
2 A DC-13 24 V at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660
0.1 A DC-13 250 V at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660
0.2 A DC-13 115 V at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660
3 A AC-15 at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660
minimum switching capacity
at 12 V 10 mA
input voltage
< 60 V X1Z2 terminal(s)
< 60 V Y1Z2 terminal(s)
maximum switching current
1 mA (X1Z2)
1 mA (Y1Z2)
input compatibility
3/4 wires sensors PNP/NPN without internal load <50 m X1Z2 terminal(s)
3/4 wires sensors PNP/NPN without internal load <50 m Y1Z2 terminal(s)
potentiometer characteristic
Linear 47 kOhm (+/- 20 %), 0.2 W, cable length <25 m Z1Z2 terminal(s)
marking
CE
overvoltage category
III conforming to IEC 60664-1
[Ui] rated insulation voltage
250 V between contact circuit and control inputs IEC certified
250 V between contact circuit and power supply IEC certified
300 V between contact circuit and control inputs CSA certified
300 V between contact circuit and power supply CSA certified
supply disconnection value
> 0.1 Uc
operating position
Any position without
surge withstand
2 kV conforming to IEC 61000-4-5 level 3
power consumption in VA
0.7 VA at 24 V
1.6 VA at 48 V
1.8 VA at 110 V
8.5 VA at 240 V
maximum power consumption in W
0.5 W at 24 V
1.2 W at 48 V
terminal description
(Y1)UNUSED
(15-16-18)OC
(Z1)UNUSED
(Z2)UNUSED
(B1-A2)CO
ALT
(X1)UNUSED
height
78 mm
width
22.5 mm
depth
80 mm
product weight
0.15 kg

Información adicional

Peso 0.29 lbs