Descripción
range |
TeSys
|
|
---|---|---|
product name |
TeSys GV3
|
|
device short name |
GV3ME
|
|
device application |
Motor
|
|
trip unit technology |
Thermal-magnetic
|
poles description |
3P
|
|
---|---|---|
network type |
AC
|
|
utilisation category |
AC-3 conforming to IEC 60947-4-1
Category A conforming to IEC 60947-2 |
|
network frequency |
50/60 Hz conforming to IEC 60947-4-1
|
|
fixing mode |
35 mm symmetrical DIN rail: clipped
Panel: screwed (with 2 x M4 screws) |
|
operating position |
Any position
|
|
motor power kW |
37 kW at 400/415 V AC 50/60 Hz
55 kW at 690 V AC 50/60 Hz 45 kW at 500 V AC 50/60 Hz |
|
breaking capacity |
100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 2 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service short-circuit breaking capacity |
100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 60 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
control type |
Push-button
|
|
[In] rated current |
80 A
|
|
thermal protection adjustment range |
56…80 A
|
|
magnetic tripping current |
1040 A
|
|
[Ue] rated operational voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Ui] rated insulation voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Ith] conventional free air thermal current |
80 A conforming to IEC 60947-4-1
|
|
[Uimp] rated impulse withstand voltage |
IEC 60947-2 6 kV
|
|
power dissipation per pole |
8 W
|
|
mechanical durability |
30000 cycles
|
|
electrical durability |
30000 cycles for AC-3 at 440 V
|
|
maximum operating rate |
25 cyc/h
|
|
rated duty |
Continuous conforming to IEC 60947-4-1
|
|
connections – terminals |
Screw clamp terminals 1 cable(s) 2.5…35 mm² solid
Screw clamp terminals 1 cable(s) 2.5…16 mm² flexible without cable end Screw clamp terminals 1 cable(s) 2.5…16 mm² flexible with cable end |
|
tightening torque |
5 N.m on screw clamp terminals
|
|
phase failure sensitivity |
Yes conforming to IEC 60947-4-1
|
|
height |
120 mm
|
|
width |
61.2 mm
|
|
depth |
113 mm
|
|
net weight |
0.7 kg
|