GV3P65

Motor circuit breaker, TeSys GV3, 3P, 48-65 A, thermal magnetic, EverLink terminals.

$160.00

GV3P65

Descripción

Main
range
TeSys
product name
TeSys GV3
device short name
GV3P
device application
Motor
trip unit technology
Thermal-magnetic
Complementary
poles description
3P
network type
AC
utilization category
AC-3 conforming to IEC 60947-4-1
Category A conforming to IEC 60947-2
network frequency
50/60 Hz conforming to IEC 60947-4-1
fixing mode
35 mm symmetrical DIN rail: clipped
Panel: screwed (with 3 x M4 screws)
operating position
Any position
motor power kW
55 kW at 690 V AC 50/60 Hz
45 kW at 500 V AC 50/60 Hz
30 kW at 400/415 V AC 50/60 Hz
breaking capacity
100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
12 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity
100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
control type
Rotary knob
[In] rated current
65 A
thermal protection adjustment range
48…65 A
magnetic tripping current
910 A
[Ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[Ith] conventional free air thermal current
65 A conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage
6 kV IEC 60947-2
power dissipation per pole
8 W
mechanical durability
50000 cycles
electrical durability
50000 cycles for AC-3 at 440 V In
maximum operating rate
25 cyc/h
rated duty
Continuous conforming to IEC 60947-4-1
connections – terminals
EverLink BTR screw connectors 2 cable(s) 1…25 mm² solid
EverLink BTR screw connectors 2 cable(s) 1…25 mm² flexible without cable end
EverLink BTR screw connectors 2 cable(s) 1…25 mm² flexible with cable end
tightening torque
5 N.m on EverLink BTR screw connectors for cable 25 mm²
8 N.m on EverLink BTR screw connectors for cable 35 mm²
suitability for isolation
Yes conforming to IEC 60947-1
phase failure sensitivity
Yes conforming to IEC 60947-4-1
height
132 mm
width
55 mm
depth
136 mm
net weight
0.96 kg
Environment
standards
EN/IEC 60947-2
EN/IEC 60947-4-1
CSA C22.2 No 60947-4-1
UL 60947-4-1
product certifications
IECEE CB Scheme
UL
CSA
CCC
EAC
ATEX
BV
LROS (Lloyds register of shipping)
DNV-GL
ABS
protective treatment
TH
IP degree of protection
IP20 conforming to IEC 60529
IK degree of protection
IK09
ambient air temperature for operation
-20…60 °C
ambient air temperature for storage
-40…80 °C
fire resistance
960 °C conforming to IEC 60695-2-1
operating altitude
3000 m
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Weight
1.016 kg
Package 1 Height
6.5 cm
Package 1 width
14.6 cm
Package 1 Length
16 cm
Unit Type of Package 2
P06
Number of Units in Package 2
120
Package 2 Weight
134.92 kg
Package 2 Height
80 cm
Package 2 width
80 cm
Package 2 Length
60 cm
Offer Sustainability
Sustainable offer status
Green Premium product
EU RoHS Directive
Mercury-free
Yes
RoHS exemption information
China RoHS Regulation
China RoHS declaration
Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins