Descripción
range of product |
TeSys D control relay
TeSys D TeSys F |
|
---|---|---|
range |
TeSys
|
|
product or component type |
Time delay auxiliary contact block
|
|
pole contact composition |
1 NO + 1 NC
|
|
connections – terminals |
Screw clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end
Screw clamp terminals 1 cable(s) 1…2.5 mm²flexible without cable end Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible without cable end Screw clamp terminals 1 cable(s) 1…2.5 mm²solid with cable end Screw clamp terminals 1 cable(s) 1…2.5 mm²solid without cable end Screw clamp terminals 2 cable(s) 1…2.5 mm²solid with cable end Screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end |
mounting location |
Front
|
|
---|---|---|
[Ui] rated insulation voltage |
600 V – certifications UL
690 V conforming to IEC 60947-5-1 600 V – certifications CSA |
|
[Ue] rated operational voltage |
690 V AC 25…400 Hz
|
|
[Ith] conventional free air thermal current |
10 A (at 60 °C)
|
|
Irms rated making capacity |
140 A at <= 690 V AC conforming to IEC 60947-5-1
250 A at <= 690 V DC conforming to IEC 60947-5-1 |
|
permissible short-time rating |
100 A 60 °C 1 s
120 A 60 °C 500 ms 140 A 60 °C 100 ms |
|
protection type |
GG fuse 10 A rating according to operational current for Ue <= 690 V
|
|
associated fuse rating |
10 A gG conforming to IEC 60947-5-1
|
|
mechanical durability |
5 Mcycles
|
|
minimum switching current |
5 mA
|
|
minimum switching voltage |
17 V
|
|
non-overlap time |
1.5 ms on de-energisation no overlap between NC and NO contact
1.5 ms on energisation no overlap between NC and NO contact |
|
timer type |
Off delay
|
|
time delay range |
10…180 s
|
|
insulation resistance |
> 10 MOhm
|