LV430406

LV430406 -Circuit breaker basic frame, Compact NSX160N, 50 kA at 415 VAC 50/60 Hz, 160 A, without trip unit, 3 poles

$380.00

Descripción

Main
range
Compact
range of product
NSX100…250
product or component type
Basic frame
device short name
Compact NSX160N
device application
Distribution
circuit breaker name
Compact NSX160N
poles description
3P
network type
AC
network frequency
50/60 Hz
[In] rated current
160 A at 40 °C
[Ui] rated insulation voltage
800 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage
8 kV conforming to IEC 60947-2
[Ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
breaking capacity code
N
breaking capacity
10 kA at 600 V AC 50/60 Hz conforming to UL 508
85 kA at 240 V AC 50/60 Hz conforming to UL 508
10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 480 V AC 50/60 Hz conforming to UL 508
36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity
10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
suitability for isolation
Yes conforming to EN 60947-2
Yes conforming to IEC 60947-2
utilisation category
Category A
pollution degree
3 conforming to IEC 60947-1

Información adicional

Peso 3.35 lbs