LV431404

LV431404 – Circuit breaker basic frame, Compact NSX250H, 70 kA at 415 VAC 50/60 Hz, 250 A, without trip unit, 3 poles

$735.00

Descripción

 

Main
range
Compact
range of product
NSX100…250
product or component type
Basic frame
device short name
Compact NSX250H
device application
Distribution
circuit breaker name
Compact NSX250H
poles description
3P
[In] rated current
250 A at 40 °C
[Ui] rated insulation voltage
800 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage
8 kV conforming to IEC 60947-2
[Ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
breaking capacity code
H
breaking capacity
85 kA at 240 V AC 50/60 Hz conforming to UL 508
65 kA at 480 V AC 50/60 Hz conforming to UL 508
10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
15 kA at 600 V AC 50/60 Hz conforming to UL 508
[Ics] rated service breaking capacity
10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
suitability for isolation
Yes conforming to EN 60947-2
Yes conforming to IEC 60947-2
pollution degree
3 conforming to IEC 60947-1

Información adicional

Peso 3.45 lbs