Descripción
range |
Compact
|
|
---|---|---|
range of product |
NSX400…630
|
|
product or component type |
Basic frame
|
|
device short name |
Compact NSX630H
|
|
device application |
Distribution
|
|
circuit breaker name |
Compact NSX630H
|
|
poles description |
3P
|
|
network type |
AC
|
|
network frequency |
50/60 Hz
|
|
[In] rated current |
630 A at 40 °C
|
|
[Ui] rated insulation voltage |
800 V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
8 kV conforming to IEC 60947-2
|
|
[Ue] rated operational voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
|
breaking capacity code |
H
|
|
breaking capacity |
85 kA at 240 V AC 50/60 Hz conforming to UL 508
65 kA at 480 V AC 50/60 Hz conforming to UL 508 100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 600 V AC 50/60 Hz conforming to UL 508 |
|
[Ics] rated service breaking capacity |
11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to EN 60947-2
Yes conforming to IEC 60947-2 |
|
utilisation category |
Category A
|
|
pollution degree |
3 conforming to IEC 60947-1
|
Valoraciones
No hay valoraciones aún.